Power System microtherm 6024gpiRemote Control DescriptionA PDA or Organizer (Handheld) with a screen resolution of 320 x 320 pixel allows the control of the system and the visualization of all relevant system values. The inverter works independently of this control unit. All selected parameters are being stored in the inverter's internal memory. Below a selection of screens is shown. If you would like to see them all, download the PDA software here and load into any PDA that runs under PALM OS5 More examples: Logging |
|
Main Screen. On top there is the menu bar. All the different
screen can be accessed from here. Below the PDA's battery charge is shown, next
right the system's date and time (there is a real
time clock in the inverter). On the left there are three buttons by which the
inverter and the genset can bei switched on and
off. Top right many system states are displayed, e.g.
genset ist starting, genset is connected in
parallel to the inverter, error messages, and so
on. Down right some system values are shown. The inverter comes with two controllable
outputs, one single phase output, and one three
phase output. You can switch the outputs with the two buttons
shown in the picture. Or you can program them, so
that the appliances are being controlled
automatically. This can be done in two additional
screens. There is not only a time control, it is
also possible to keep the outputs inactive outside
of genset running times. If you would like to have a "must start", you
can adjust it here. These are the parameters for the automatic
start. Adjust here low battery start and load
start The current compensation modifies the low
battery cut out voltage. When the batteries are
small or the cables long, then this value is rather
high. During night time the genset should run only if
absolutely necessary. The quiet time can be
selected here. In all circumstances the genset is being stopped
at tthe voltage selected here (normally 28.8V). In case above "equalize once per month" had been
selected, the stop voltage will be higher
(typically 31V). The genset run time can be limited to avoid
excessive run times (half an hour is not really
excessive). |